ANSI/ASHRAE 110 face velocity checks for laboratory fume hoods
ANSI/ASHRAE 110, the Method of Testing Performance of Laboratory Fume Hoods, provides a repeatable way to assess fume hood performance. Face velocity checks matter in Australian research, healthcare and industrial facilities because sash position, traffic and exhaust balance can alter the air reaching a worker.
Face velocity is air speed at the hood opening, reported in metres per second (m/s) or feet per minute (fpm). It indicates capture potential but does not prove containment. A reliable record combines test conditions, representative readings, calibration details and observations of cross-drafts, obstructions and sash position.
Why laboratory fume hood face velocity matters
A fume hood uses controlled exhaust flow to carry airborne chemicals away from the breathing zone. Air speed and pattern at the opening influence whether a contaminant released near the work surface is drawn in. Low flow can weaken capture, while excessive or uneven flow can disturb the plume and create turbulence.
The standard places these observations within a formal test method. It defines the configuration, sampling approach and reporting needed to compare results across commissioning, maintenance and incident investigations. Performance must be assessed in context: sash height, filter loading, traffic and nearby extraction systems can all change the result.
Format and convenience influence purchasing in every technical market. As flower versus pre-roll choices shows in another consumer market, buyers respond to convenience and consistency; laboratories need a correctly identified PDF that remains usable at the bench or in the field.
Preparing and measuring the hood
Start with the hood's intended operating condition. Decide whether the check represents normal work, a specified sash height, commissioning or troubleshooting, then use the current edition's sampling locations and settings. Keep the hood running in its normal exhaust configuration and control doors, windows and traffic as far as practical.
Use a calibrated directional anemometer or suitable thermal anemometer for low-speed airflow. Check zero drift, orientation and resolution, then measure across the opening rather than at the centre alone. The centre can hide a slow corner, strong jet or turbulence from an obstruction. Record each position and retain the raw values.
The test record should identify the instrument and calibration status, date, hood number, sash height, room conditions and hood operating state. Note cross-drafts from air-conditioning jets, open doors or neighbouring hoods. These details may explain an acceptable average that still corresponds to poor performance.
Interpreting airflow and containment
Begin with the average face velocity and spread of readings. A common design target is about 0.5 m/s, approximately 100 fpm, but the governing value comes from the current standard, manufacturer instructions and risk assessment. Australian specifications often use metric units; include both units when an older or international record is involved.
Distribution matters as much as the mean. A centre reading at target can conceal a slow edge, strong jet or reversed flow caused by room pressure. Compare the minimum, maximum and variation against the applicable acceptance criteria. For low airflow, inspect the sash, filters, ductwork and controls; for erratic results, investigate cross-drafts, competing exhaust systems and pressure balance.
Containment remains the safety question. Face velocity cannot show whether a released contaminant reaches the exhaust, while airflow visualisation can reveal turbulence hidden by a single number. The same controlled-evidence discipline appears in IPC-9201 reliability testing methods, where repeatable procedures support sound engineering decisions. Repeat the same grid after adjustments and retain before-and-after results.
Australian laboratory considerations
Conditions vary across Australian facilities. A Sydney university laboratory may have strong afternoon air-conditioning and frequent door traffic; a Melbourne analytical site may switch heating, cooling and exhaust through the seasons; and a Brisbane testing laboratory may operate in warm, humid conditions. These factors can influence room pressure and operator behaviour, making test context part of the evidence.
Use local references alongside the method. Teams can coordinate face velocity checks with AS/NZS 2100 for laboratory environmental hazards, Safe Work Australia risk controls and NATA accreditation processes under ISO/IEC 17025 where applicable. Building approvals, chemical hygiene plans and manufacturer service instructions may add site-specific requirements. The recognised test framework supports, rather than replaces, the local risk assessment.
Digital purchasing suits Australian operations. A PDF can reach teams in Melbourne, Brisbane and Perth without international freight or the customs process for imported print copies. For a hard copy, check Australian Customs, GST and courier obligations with the seller or a licensed broker. The revision named in the contract and quality system matters more than a similar title.
A practical testing and purchasing checklist
Document Bays offers downloadable PDF copies of industry standards and engineering codes from organisations including ANSI, ASME, API, AWS, ASHRAE and JIS. Buyers can review current standards pricing, select the required revision and obtain immediate digital access, with multiple currencies and major payment methods available. Confirm that the file is legible, searchable and suitable for on-site use.
Pair the reference with a local procedure defining responsibilities, test conditions and acceptance criteria. Commissioning, scheduled maintenance and post-repair verification are different activities even when the same instrument is used. Keep original readings with the applicable revision so an auditor or building owner can reconstruct the decision.
Before the test
- Confirm the applicable ANSI/ASHRAE revision, hood manual and local risk assessment.
- Verify the anemometer calibration, zero response and directional performance.
- Record sash height, hood operating state, room conditions and cross-drafts.
- Mark sampling positions and photograph any unusual hood configuration.
After the test
- Report individual readings, average velocity, minimum, maximum and spread.
- Compare results with the specified acceptance criteria and document deviations.
- Investigate failed or uneven airflow before chemicals are handled at the hood.
- Retest after adjustments and retain instrument and revision details.
| Aspect | Face velocity check | Containment-focused check |
|---|---|---|
| Purpose | Measures airflow into the hood | Assesses airborne-material control |
| Evidence | Grid readings and operating state | Release test and airflow observations |
| Strength | Finds low or uneven face airflow | Addresses capture at the work area |
| Limitation | Does not prove containment | Needs controlled conditions and trained personnel |
Choose the current ANSI/ASHRAE 110 document from Document Bays, download it for immediate use and establish a consistent laboratory fume hood testing procedure across your quality system.
Quick Inquiry
Questions about an order or a specific standard? Use our contact form.
Contact UsSecure payment with SSL
Featured Products
About Standards Store
We provide industry standards and codes in PDF format for immediate download. Our catalog spans engineering, manufacturing, construction, and quality management — with documents from over 50 issuing bodies worldwide.
Learn MoreLatest Additions
Recently added standards include AWS D14.4/D14.4M-2019, API RP 581-2019, ISO/IEC 17025:2017, RTCA DO-363, and IPC/ECA J-STD-002E. Visit the New Standards section for the complete list.
New StandardsSecure Payment
All transactions are protected with SSL encryption. We accept Visa, Mastercard, and PayPal. Use coupon codes at checkout for additional discounts on eligible items.
Payment InfoStandards Store is dedicated to making technical standards and codes accessible to professionals worldwide. Every document in our catalog is delivered as a PDF for immediate download — no shipping, no waiting. We serve engineers, quality assurance specialists, manufacturers, and contractors who rely on accurate, up-to-date standards for their work.
Browse by issuing organization, explore new additions, or check our specials for discounted titles.
For questions about an order or for information about our products, please use the contact form below. Select the appropriate subject — Customer Service for order inquiries or Webmaster for technical issues with the website.
We aim to respond promptly to all inquiries.
Send a Message
Standards Store offers PDF downloads of industry standards and codes. All product listings and prices shown are historical and may not reflect current availability. Standards documents are provided in electronic PDF format only; physical copies are not offered. The organizations whose standards appear in our catalog — including ANSI, ASME, API, SAE, AWS, ASHRAE, CSA, JIS, IPC, TIA, VDI, and others — are independent entities. Listing their documents does not imply endorsement or authorized distributor status. Payment is processed securely via SSL using Visa, Mastercard, or PayPal. Coupon discounts may be available on select items. For questions, use the contact form on this page.